Ducting and duct sizing.


AIR DISTRIBUTION SYSTEM/DUCTING OR DUCT DESIGN

What is a duct?

A duct in HVAC (Heating, Ventilation and Air conditioning) is used as a medium or path to transfer air  from air conditioning units to conditioned space. Its used for exhaust and ventilation purpose as shown in figure below. A duct is constructed from a material with very low surface friction properties to reduce static pressure on air conditioning unit blower. A ducting system is used for supply, return, exhaust (kitchen and toilets), ventilation and fresh air supply to conditioned space. Duct may be of different shapes spiral (rounded), rectangular or square shape. A rounded duct may be flexible to make easy connection with air terminals like diffusers or registers. The duct which carries cool air from air conditioning unit is properly sealed and insulated with high thermal resistance property material to reduce cooling loss, both supply and return air ducts are insulated. But exhaust air ducts don’t need insulation.

A duct is created from joining different pieces like rectangular straight pieces, transducers (concentric or in-centric), bends and offsets. 
Air distribution is combination of Air delivering source, Duct distribution including fittings, dampers, registers, grills etc. In this article duct design calculations, duct routing best selection will be thoroughly studied. SMACNA standard is followed for duct construction.



Types of Ducting in HVAC:-

1.   Supply air duct: - Supply air duct is the path through which we deliver conditioned air to the space which is needed to air conditioned. The air is dropped through grills, diffusers or registers at different points. Supply air ducts are always shown in the system with green color.
2.     Return air duct: - Return air duct as name suggests it’s a path through which the cool air after gaining heat from the conditioned space is taken back to the air source like FCU, AHU etc.  Return air duct has always 5-10% more duct size as compared to supply air duct. Return air ducts are drawn in drawing with red colors.
3.     Exhaust air duct: - For ventilation purpose or to maintain air quality in the conditioned space exhaust of air is needed and this is done through a duct installed separately. 
4.     Fresh air duct: - Fresh air duct is installed to maintain air quality and this duct does not bring fresh air from outside directly inside the room. Fresh air is always dropped first at the suction side of air source. 
5.     Kitchen exhaust duct: - The kitchen exhaust duct through the oily air and smoke to the environment but there is a bit of trick to do that. This air is first treated and then left in the environment following the norms of green building.
6.     Toilet exhaust duct: - This duct simply carries away all exhaust from the toilets to the environment.

How to design or size a duct?

Before duct sizing we need to calculate heat load and from heat load we get TR, CFM and a check figure is considered as follows: -

CFM/Area and sq.ft/TR

For example – we have calculated heat load for a building which is 10 TR, CFM are 300 CFM and area is 600sq.ft. What will be TR/Sq.ft and CFM/sq.ft.

CFM/Sq.ft = 600/300 = 2 cfm/sq.ft

And

sq.ft/TR means how much are will be covered by 1TR.

  600/10 = 60 sq.ft/ TR
 This total are 600 sq. ft is for all parts like there may three bed rooms and a dining room and a guest room. So what we will do we will calculate the areas separately for each and then calculate the CFM for each room.

For example - area of a bed room is 10 X 20 = 200 sq.ft 
Then, CFM = 200 X 2 cfm (From chech figure) = 400 CFM

In the same way each separate area and CFM will be calculated and using friction chart we will get sizes of ducts.

Important Note: - The above example was only for reference but actual calculation will give accurate cfm/sq.ft and sq.ft/TR. Which is recommended as 2-4cfm/sq.ft and 200-350 sq.ft/TR.

HOW TO SIZE?

Before sizing a duct you should be aware about some standards.

1.     Aspect ratio 4:1 means the ratio of width and height should not go above this ratio because higher the aspect ratio higher will be the surface area and higher the Static pressure. Higher aspect ratio increases the cost of installation and operation cost as well.
2.      The duct class is considered for duct sizing. Duct class varies from class 1 to 6. Higher the duct class higher will be installation cost, more weight of material, thickness will increase which will be difficult to bend and at site no fabrication can be done. So lowest duct class is considered at smallest aspect ratio.
3.     Rating of galvanizing for duct material is recommended to G75 or G90.
4.     Type of class of fittings. There are two types of ducting fittings one is class A and other is Class B.
In class A we use collars, bends, shoe-pieces etc for braches. This type of fitting has lowest cost of installation but higher operational cost.
In class B we use only y-pieces for branch ducts and this type of fitting has higher cost of installation and lower operating cost.
For sizing a linear equation and a friction chart is considered as below from which we get duct sizes for main and branch air ducts. From chart we get duct size as equivalent dia and afterwards we convert it to rectangular size with help of a software which is duct sizer.


Linear equation
                            Q = AV
Where Q is air flow (CFM)
           A is area of duct cross section sq.ft.
           V is velocity (FPM) Feet/minute


1.      ACCORDING TO VELOCITY

1.1. Low velocity or High velocity system.
1.2. Low pressure or High pressure system.

These systems are further classified as following:-

COMFORT AIR CONDITIONING SYSTEM - LOW VELOCITY (1200-2200FPM) & HIGH VELOCITY (2500-3000FPM)

INDUSTRIAL AIR CONSITIONING SYSTEM- 2200-2500FPM & 2500-5000 FPM

Air velocity is taken according to the sound levels which is called Noise criteria and recommended as follow: -

APPLICATION
NC levels (DB)
Bed Room
20-25
Hall or Office
30
Toilet/kitchen
35-40
Workshop
50

Where 200 FPM = 1 M/s

 For residential air conditioning generally velocity is taken from 1200-1400 FPM for noise control.

For return air ducts only low velocity is considered and 20 % less than supply air ducts.

2.     ACCORDING TO PRESSURE (TOTAL P = SP+VP)
2.1. Low Pressure – Upto 3 ¾” WG.
2.2. Medium Pressure 3 ¾” – 6 ¾” WG.
2.3. High Pressure 6 ¾” – 12 ¾” WG.

Where 1’’ of water gauge = 250 pascals




There are three methods to size a duct

1.    Equal Friction method: -
1.1.         This method of sizing is used for supply, exhaust and return air duct.
1.2.         In this method same friction loss per ft is taken for entire length.
1.3.         The velocity is selected from the table with sound level being limiting factor.
1.4.     The velocity is selected from the first piece of duct from starting from the fan and considered same for entire length.
1.5.         Only this method is most reliable and used for duct sizing in HVAC.

2.   Velocity reduction method
3.    Static regain method
Best route for ducting in a building: - Duct rout is always selected where we avoid diversions, offsets and bends. A straight path is always considered like corridor is the best place to run the duct and supply branches are dropped same as shown in figure below. A symmetrical diffuser placement is always preferred for best cooling and design. For exhaust air ducts shafts and cut outs are considered by the co-ordination of civil, architect and HVAC engineers and all other agencies.
Recommended thickness according to size of duct
Gauge
Thickness(mm)
Size (Width)
26 g
0.6
0-400
24g
0.7
401-750
22g
0.8
751-1050
20g
1.0
1100-1500
18g
1.2
Above 1500


Recommended air guiding vanes criteria

Upto 400 width
No vanes
Short radius L-bow 90’
401-800
1 vane
801-1200
2 vanes
Above 1200
3 vanes







Post a Comment (0)
Previous Post Next Post